| 12 | AutoPing Timeout | Target IP Address | # fails before action | -- | IP Address to Ping. Failure to ping creates trigger. |
| 13 | Inlet Line Max Current Threshold | Inlet Line | Amperage Threshold | # secs past threshold | Applies to 3 phase PDUs with line measurements. Amperage threshold in amps |
| 14 | Inlet Line Min Current Threshold | Inlet Line | Amperage Threshold | # secs past threshold | Applies to 3 phase PDUs with line measurements. Amperage threshold in amps |
| 15 | Inlet Max Current Threshold | Inlet ID | Amperage Threshold | # secs past threshold | Applies to single phase PDUs. Amperage threshold in amps |
| 16 | Inlet Min Current Threshold | Inlet ID | Amperage Threshold | # secs past threshold | Applies to single phase PDUs. Amperage threshold in amps |
| 17 | Inlet Max Voltage Threshold | Inlet ID | Voltage Threshold | # secs past threshold | Applies to single phase PDUs. Voltage threshold in volts |
| 18 | Inlet Min Voltage Threshold | Inlet ID | Voltage Threshold | # secs past threshold | Applies to single phase PDUs. Voltage threshold in volts |
| 19 | Inlet Max Line Frequency Threshold | Inlet ID | Line Frequency Threshold | # secs past threshold | Applies to single phase PDUs. Line frequency threshold in hertz |
| 20 | Inlet Max Line Frequency Threshold | Inlet ID | Line Frequency Threshold | # secs past threshold | Applies to single phase PDUs. Line frequency threshold in hertz |
| 21 | Inlet Min Power Factor | Inlet ID | Power Factor Threshold | # secs past threshold | Power Factor Threshold as a ratio |
| 22 | Inlet Active Energy Accumulation Max | Inlet ID | kWh Threshold | -- | -- |
| 24 | Inlet Min Active Power Threshold | Inlet ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
| 23 | Inlet Max Active Power Threshold | Inlet ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
| 25 | Inlet Max Apparent Power Threshold | Inlet ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
| 26 | Inlet Min Apparent Power Threshold | Inlet ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
| 29 | Inlet 3 Phase Imbalance | Inlet ID | % Imbalance Threshold | # secs past threshold | -- |
| 30 | Bank Circuit Breaker Trip | Bank ID | -- | -- | -- |
| 31 | Bank Max Current Threshold | Bank ID | Amperage Threshold | # secs past threshold | Amperage threshold in amps |
| 32 | Bank Min Current Threshold | Bank ID | Amperage Threshold | # secs past threshold | Amperage threshold in amps |
| 33 | Bank Max Voltage Threshold | Bank ID | Voltage Threshold | # secs past threshold | Voltage threshold in volts |
| 34 | Bank Min Voltage Threshold | Bank ID | Voltage Threshold | # secs past threshold | Voltage threshold in volts |
| 35 | Bank Max Line Frequency Threshold | Bank ID | Line Frequency Threshold | # secs past threshold | Line Frequency threshold in hertz |
| 36 | Bank Min Line Frequency Threshold | Bank ID | Line Frequency Threshold | # secs past threshold | Line Frequency threshold in hertz |
| 37 | Bank Min Power Factor | Bank ID | Power Factor Threshold | # secs past threshold | |
| 38 | Bank Active Energy Accumulation Max | Bank ID | kWh Threshold | -- | |
| 39 | Bank Max Active Power Threshold | Bank ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
| 40 | Bank Min Active Power Threshold | Bank ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
| 41 | Bank Max Apparent Power Threshold | Bank ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
| 42 | Bank Min Apparent Power Threshold | Bank ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
| 45 | Outlet Max Current Threshold | Outlet ID | Amperage Threshold | # secs past threshold | Applies to PDUs with Outlet Current Measurements. Amperage threshold in amps |
| 46 | Outlet Min Current Threshold | Outlet ID | Amperage Threshold | # secs past threshold | Applies to PDUs with Outlet Current Measurements. Amperage threshold in amps |
| 49 | Temperature Max Threshold | Sensor ID | Temperature Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Temperature threshold in celsius |
| 50 | Temperature Min Threshold | Sensor ID | Temperature Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Temperature threshold in celsius |
| 51 | Humidity Max Threshold | Sensor ID | Humidity Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Humidity threshold as relative humidity % |
| 52 | Humidity Min Threshold | Sensor ID | Humidity Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Humidity threshold as relative humidity % |
| 53 | Scheduled Daily Time | Time to trigger | -- | -- | Time of day in military time. example: 13:01 |
| 54 | Scheduled Time Interval | -- | -- | -- | Triggers every X seconds forever |
| 55 | ATS Switched to Secondary | -- | -- | -- | Applies to ATS PDUs. Triggers when Primary ATS Inlet has lost power and switches to Secondary |
| 56 | ATS Switched to Primary | -- | -- | -- | Applies to ATS PDUs. Triggers when Primary ATS Inlet has recovered and switches from Secondary to Primary |
| 57 | Secondary Power Source Lost | -- | -- | -- | Applies to ATS PDUs. Triggers when Secondary ATS Inlet has lost power. |
| 58 | Secondary Power Source Restored | -- | -- | -- | Applies to ATS PDUs. Triggers when Secondary ATS Inlet has recovered power. |