12 | AutoPing Timeout | Target IP Address | # fails before action | -- | IP Address to Ping. Failure to ping creates trigger. |
13 | Inlet Line Max Current Threshold | Inlet Line | Amperage Threshold | # secs past threshold | Applies to 3 phase PDUs with line measurements. Amperage threshold in amps |
14 | Inlet Line Min Current Threshold | Inlet Line | Amperage Threshold | # secs past threshold | Applies to 3 phase PDUs with line measurements. Amperage threshold in amps |
15 | Inlet Max Current Threshold | Inlet ID | Amperage Threshold | # secs past threshold | Applies to single phase PDUs. Amperage threshold in amps |
16 | Inlet Min Current Threshold | Inlet ID | Amperage Threshold | # secs past threshold | Applies to single phase PDUs. Amperage threshold in amps |
17 | Inlet Max Voltage Threshold | Inlet ID | Voltage Threshold | # secs past threshold | Applies to single phase PDUs. Voltage threshold in volts |
18 | Inlet Min Voltage Threshold | Inlet ID | Voltage Threshold | # secs past threshold | Applies to single phase PDUs. Voltage threshold in volts |
19 | Inlet Max Line Frequency Threshold | Inlet ID | Line Frequency Threshold | # secs past threshold | Applies to single phase PDUs. Line frequency threshold in hertz |
20 | Inlet Max Line Frequency Threshold | Inlet ID | Line Frequency Threshold | # secs past threshold | Applies to single phase PDUs. Line frequency threshold in hertz |
21 | Inlet Min Power Factor | Inlet ID | Power Factor Threshold | # secs past threshold | Power Factor Threshold as a ratio |
22 | Inlet Active Energy Accumulation Max | Inlet ID | kWh Threshold | -- | -- |
24 | Inlet Min Active Power Threshold | Inlet ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
23 | Inlet Max Active Power Threshold | Inlet ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
25 | Inlet Max Apparent Power Threshold | Inlet ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
26 | Inlet Min Apparent Power Threshold | Inlet ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
29 | Inlet 3 Phase Imbalance | Inlet ID | % Imbalance Threshold | # secs past threshold | -- |
30 | Bank Circuit Breaker Trip | Bank ID | -- | -- | -- |
31 | Bank Max Current Threshold | Bank ID | Amperage Threshold | # secs past threshold | Amperage threshold in amps |
32 | Bank Min Current Threshold | Bank ID | Amperage Threshold | # secs past threshold | Amperage threshold in amps |
33 | Bank Max Voltage Threshold | Bank ID | Voltage Threshold | # secs past threshold | Voltage threshold in volts |
34 | Bank Min Voltage Threshold | Bank ID | Voltage Threshold | # secs past threshold | Voltage threshold in volts |
35 | Bank Max Line Frequency Threshold | Bank ID | Line Frequency Threshold | # secs past threshold | Line Frequency threshold in hertz |
36 | Bank Min Line Frequency Threshold | Bank ID | Line Frequency Threshold | # secs past threshold | Line Frequency threshold in hertz |
37 | Bank Min Power Factor | Bank ID | Power Factor Threshold | # secs past threshold | |
38 | Bank Active Energy Accumulation Max | Bank ID | kWh Threshold | -- | |
39 | Bank Max Active Power Threshold | Bank ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
40 | Bank Min Active Power Threshold | Bank ID | Active Power Threshold | # secs past threshold | Active Power Threshold in watts |
41 | Bank Max Apparent Power Threshold | Bank ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
42 | Bank Min Apparent Power Threshold | Bank ID | Apparent Power Threshold | # secs past threshold | Apparent Power Threshold in volt-amperes (VA) |
45 | Outlet Max Current Threshold | Outlet ID | Amperage Threshold | # secs past threshold | Applies to PDUs with Outlet Current Measurements. Amperage threshold in amps |
46 | Outlet Min Current Threshold | Outlet ID | Amperage Threshold | # secs past threshold | Applies to PDUs with Outlet Current Measurements. Amperage threshold in amps |
49 | Temperature Max Threshold | Sensor ID | Temperature Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Temperature threshold in celsius |
50 | Temperature Min Threshold | Sensor ID | Temperature Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Temperature threshold in celsius |
51 | Humidity Max Threshold | Sensor ID | Humidity Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Humidity threshold as relative humidity % |
52 | Humidity Min Threshold | Sensor ID | Humidity Threshold | # secs past threshold | Requires attached temperature/humidity sensor. Humidity threshold as relative humidity % |
53 | Scheduled Daily Time | Time to trigger | -- | -- | Time of day in military time. example: 13:01 |
54 | Scheduled Time Interval | -- | -- | -- | Triggers every X seconds forever |
55 | ATS Switched to Secondary | -- | -- | -- | Applies to ATS PDUs. Triggers when Primary ATS Inlet has lost power and switches to Secondary |
56 | ATS Switched to Primary | -- | -- | -- | Applies to ATS PDUs. Triggers when Primary ATS Inlet has recovered and switches from Secondary to Primary |
57 | Secondary Power Source Lost | -- | -- | -- | Applies to ATS PDUs. Triggers when Secondary ATS Inlet has lost power. |
58 | Secondary Power Source Restored | -- | -- | -- | Applies to ATS PDUs. Triggers when Secondary ATS Inlet has recovered power. |