Home

Event Codes Table

CodeNameParameter 1Parameter 2Parameter 3Description
12AutoPing TimeoutTarget IP Address# fails before action--IP Address to Ping. Failure to ping creates trigger.
13Inlet Line Max Current ThresholdInlet LineAmperage Threshold# secs past thresholdApplies to 3 phase PDUs with line measurements. Amperage threshold in amps
14Inlet Line Min Current ThresholdInlet LineAmperage Threshold# secs past thresholdApplies to 3 phase PDUs with line measurements. Amperage threshold in amps
15Inlet Max Current ThresholdInlet IDAmperage Threshold# secs past thresholdApplies to single phase PDUs. Amperage threshold in amps
16Inlet Min Current ThresholdInlet IDAmperage Threshold# secs past thresholdApplies to single phase PDUs. Amperage threshold in amps
17Inlet Max Voltage ThresholdInlet IDVoltage Threshold# secs past thresholdApplies to single phase PDUs. Voltage threshold in volts
18Inlet Min Voltage ThresholdInlet IDVoltage Threshold# secs past thresholdApplies to single phase PDUs. Voltage threshold in volts
19Inlet Max Line Frequency ThresholdInlet IDLine Frequency Threshold# secs past thresholdApplies to single phase PDUs. Line frequency threshold in hertz
20Inlet Max Line Frequency ThresholdInlet IDLine Frequency Threshold# secs past thresholdApplies to single phase PDUs. Line frequency threshold in hertz
21Inlet Min Power FactorInlet IDPower Factor Threshold# secs past thresholdPower Factor Threshold as a ratio
22Inlet Active Energy Accumulation MaxInlet IDkWh Threshold----
24Inlet Min Active Power ThresholdInlet IDActive Power Threshold# secs past thresholdActive Power Threshold in watts
23Inlet Max Active Power ThresholdInlet IDActive Power Threshold# secs past thresholdActive Power Threshold in watts
25Inlet Max Apparent Power ThresholdInlet IDApparent Power Threshold# secs past thresholdApparent Power Threshold in volt-amperes (VA)
26Inlet Min Apparent Power ThresholdInlet IDApparent Power Threshold# secs past thresholdApparent Power Threshold in volt-amperes (VA)
29Inlet 3 Phase ImbalanceInlet ID% Imbalance Threshold# secs past threshold--
30Bank Circuit Breaker TripBank ID------
31Bank Max Current ThresholdBank IDAmperage Threshold# secs past thresholdAmperage threshold in amps
32Bank Min Current ThresholdBank IDAmperage Threshold# secs past thresholdAmperage threshold in amps
33Bank Max Voltage ThresholdBank IDVoltage Threshold# secs past thresholdVoltage threshold in volts
34Bank Min Voltage ThresholdBank IDVoltage Threshold# secs past thresholdVoltage threshold in volts
35Bank Max Line Frequency ThresholdBank IDLine Frequency Threshold# secs past thresholdLine Frequency threshold in hertz
36Bank Min Line Frequency ThresholdBank IDLine Frequency Threshold# secs past thresholdLine Frequency threshold in hertz
37Bank Min Power FactorBank IDPower Factor Threshold# secs past threshold
38Bank Active Energy Accumulation MaxBank IDkWh Threshold--
39Bank Max Active Power ThresholdBank IDActive Power Threshold# secs past thresholdActive Power Threshold in watts
40Bank Min Active Power ThresholdBank IDActive Power Threshold# secs past thresholdActive Power Threshold in watts
41Bank Max Apparent Power ThresholdBank IDApparent Power Threshold# secs past thresholdApparent Power Threshold in volt-amperes (VA)
42Bank Min Apparent Power ThresholdBank IDApparent Power Threshold# secs past thresholdApparent Power Threshold in volt-amperes (VA)
45Outlet Max Current ThresholdOutlet IDAmperage Threshold# secs past thresholdApplies to PDUs with Outlet Current Measurements. Amperage threshold in amps
46Outlet Min Current ThresholdOutlet IDAmperage Threshold# secs past thresholdApplies to PDUs with Outlet Current Measurements. Amperage threshold in amps
49Temperature Max ThresholdSensor IDTemperature Threshold# secs past thresholdRequires attached temperature/humidity sensor. Temperature threshold in celsius
50Temperature Min ThresholdSensor IDTemperature Threshold# secs past thresholdRequires attached temperature/humidity sensor. Temperature threshold in celsius
51Humidity Max ThresholdSensor IDHumidity Threshold# secs past thresholdRequires attached temperature/humidity sensor. Humidity threshold as relative humidity %
52Humidity Min ThresholdSensor IDHumidity Threshold# secs past thresholdRequires attached temperature/humidity sensor. Humidity threshold as relative humidity %
53Scheduled Daily TimeTime to trigger----Time of day in military time. example: 13:01
54Scheduled Time Interval------Triggers every X seconds forever
55ATS Switched to Secondary------Applies to ATS PDUs. Triggers when Primary ATS Inlet has lost power and switches to Secondary
56ATS Switched to Primary------Applies to ATS PDUs. Triggers when Primary ATS Inlet has recovered and switches from Secondary to Primary
57Secondary Power Source Lost------Applies to ATS PDUs. Triggers when Secondary ATS Inlet has lost power.
58Secondary Power Source Restored------Applies to ATS PDUs. Triggers when Secondary ATS Inlet has recovered power.